Earth Resistance Range : 0.20 Ω (0.01 Ω resolution) to 1600 Ω (20 Ω resolution), 10 ranges, Zero suppression: Less than 0.02 Ω,
Accuracy: ±1.5 % rdg. ±0.02 Ω
AC Current Range : 20.00 mA (0.01 mA resolution) to 60.0 A (0.1 A resolution), 5 ranges, Zero suppression: Less than 0.05 mA,
Accuracy: ±2.0 % rdg. ±0.05 mA (30 Hz to 400 Hz, True RMS), Crest factor 5.0 or less (for the 60 A range, 1.7 or less)
Maximum input current (Current measurement) : 100 A AC continuous, AC 200 A for 2 minutes or shorter (at 50 Hz/60 Hz, requires derating at frequency)
Maximum rated terminal-to-ground voltage : 600 VAC measurement category IV (anticipated transient overvoltage 8000 V)
Memory Function : 2000 data
Alarm Function : For resistance measurement and current measurement, Beeps when measured value is less than or greater than threshold.
Harmonic Levels : [With Z3210 installed] Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio
*Harmonics can be displayed with our free app GENNECT Cross.
Other functions : Data hold, Backlight, Filter, Auto power save, Wireless communication (without Z3210 installed))
Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
Measure load current up to 60.0 A range
Clamp at the narrowest point
Earth resistance measurement for multi-grounded systems
Measure leak current with absolute certainty with highly sensitive 0.01 mA resolution (at 20.00 mA range)
Measurement Principle : Instrument has two cores for voltage injection and current measurement. From the defined voltage and measured current, the total circuit loop resistance is calculated
Note: For multi grounded systems only. In a multi-grounded system, the larger the number of grounding poles, the more accurate the measured value.
Test Voltage : 250 V to 5.00 kV DC, (Possible in 25 V steps between 250 V and 1 kV and in 100 V steps between 1 and 5 kV)
Measurement Range :
0.00 MΩ to 500 GΩ (250 V)
0.00 MΩ to 1.00 TΩ (500 V)
0.00 MΩ to 2.00 TΩ (1 kV)
0.00 MΩ to 5.00 TΩ (2.5 kV)
0.00 MΩ to 10.0 TΩ (5 kV)
Measurement Current : 1 mA (Test voltage 250 V to 1.00 kV), 0.5 mA (Test voltage 1.10 kV to 2.50 kV) 0.25 mA (Test voltage 2.60 kV to 5.00 kV), Short-circuit current: 2 mA or less
Resistance Range : 10 MΩ to 10 TΩ, 7 ranges (auto range)
Accuracy :
±5% rdg. ±5 dgt. Up to [Test voltage (setting value)/Resistance measurable at 100 nA]
±20% rdg. ±5 dgt. [Test voltage (setting value)/Resistance measurable at 100 nA] to [Test voltage (setting value)/Resistance measurable at 1 nA] or 500 GΩ
±30% rdg. ±50 dgt. [Test voltage (setting value)/Resistance measurable at 1 nA] or 501 GΩ to 9.99 TΩ
Leakage current measurement : 1.00 nA to 1.20 mA, 6 ranges (current measurement that occurs when test voltage is generated)
Accuracy ±2.5% rdg. ±5 dgt. (1 mA range); refer to complete catalog for other ranges
Voltage measurement : ±50 V to ±1.00 kV DC, 50 V to 750 V AC (50/60 Hz),
Accuracy: ±5 % rdg. ±5 dgt. , Input resistance: Approx. 10 MΩ
Temperature measurement : -10.0 ˚C to 70.0 ˚C, 3 ranges (used with optional sensor)
Accuracy ±1.0 ˚C (0.0 ˚C to 40.0 ˚C); refer to complete catalog for other ranges
Other Functions : Insulation Diagnosis (Temperature compensation, PI/DAR display, Step voltage test), Data memory, Communication (USB 2.0, PC application software), auto discharge, hot conductor warning indication, etc.
Digital LCD, max. 999 dgt. with backlight, Bar graph display
Dimensions and Mass : 260 mm (10.24 in)W × 250.6 mm (9.87 in)H × 119.5 mm (4.70 in)D, 2.8 kg (98.8 oz)
Included Accessories : Test lead 9750-01 ×1, Test lead 9750-02 ×1, Test lead 9750-03 ×1, Alligator clip 9751-01 ×1, Alligator clip 9751-02 ×1, Alligator clip 9751-03 ×1, Instruction manual ×1, LR6 (AA) alkaline batteries ×6, USB cable ×1, PC application software (CD-R) ×1
FEATURES
Measure insulation of high-voltage equipment (such as transformers, cables, and motors)
Wide testing voltage range, up to 5.00 kV from 250 V DC
Wide measurement insulation range, up to 10 TΩ
PI (Polarization Index) and DAR (Dielectric Absorption Ratio) automatically calculated / display
Extended operating temperature range of -10°C to 50°C
Maximum rated line-to-ground voltage
1000 V (Measurement Category IV), Anticipated transient overvoltage 12000 V
2000 V (Measurement Category III), Anticipated transient overvoltage 15000 V
Input Resistance : 20 MΩ ±5.0% (between INPUT H and INPUT L, when OUTPUT terminal is open)
Overload Protection :
2200 V DC/2200 V AC (applied for 1 minute) (between INPUT H and INPUT L)
600 V DC/600 V AC (applied for 1 minute) (between OUTPUT H and OUTPUT L)
Output Terminal : 4 mm banana terminal
Operating Temperature Range : -25°C to 65°C (-13°F to 149°F)
Operating Humidity Range : −25°C to 40°C (−13°F to 104°F): 80% RH or less (non-condensing)
40°C to 65°C (104°F to 149°F): Linearly reduces from 80% RH or less at 40°C (104°F) to 25% RH or less at 65°C (149°F) (non-condensing)
Storage temperature and humidity range : -30°C to 70°C (-22°F to 158°F) 90% RH or less (non-condensing)
Standards : EN 61010
Included Accessories : Connection Cable Set L4943 ×1, Strap with buckle ×2, Strap ×1, Carrying Case C0205 ×1, Instruction Manual ×1, Operating Precautions ×1
FEATURES
Enables high voltage measurement up to CAT Ⅲ 2000 V
Safely measure solar installations like the mega-solar without interrupting the grid
Connects to compatible Hioki clamp meters and digital multimeters (DMMs)
ACCURACY FOR COMPATIBLE INSTRUMENTS
DT-4261 :
Range 600.0 V: Combined accuracy ±0.5% rdg ±0.2 V
Range 2000 V: Combined accuracy ±0.5% rdg ±5 V
CM4141-50 ; CM4371-50 ; CM4373-50 ; CM4375-50 :
Range 600.0 V: Combined accuracy ±1.0% rdg ±0.3 V
Range 2000 V: Combined accuracy ±1.0% rdg ±3 V
DT-4282 ; DT-4281 :
Range 60.000 V: Combined accuracy ±0.8% rdg ±0.002 V (output rate 1/10)
Range 600.00 V: Combined accuracy ±0.8% rdg ±0.02 V (output rate 1/10)
DT-4252 ; DT-4253 :
Range 60.00 V: Combined accuracy ±1.2% rdg ±0.05 V (output rate 1/10)
Range 600.0 V: Combined accuracy ±1.2% rdg ±0.5 V (output rate 1/10)
DT-4255 ; DT-4256 :
Range 60.00 V: Combined accuracy ±1.2% rdg ±0.03 V (output rate 1/10)
Range 600.0 V: Combined accuracy ±1.2% rdg ±0.3 V (output rate 1/10)